Welcome to an exploration of rooftop units (RTUs) in HVAC systems. This article will guide you through what RTUs are, their applications, how they function, the various types available, and the key components that make them work efficiently. Let’s delve into the world of RTUs and enhance your understanding of these essential systems.
Rooftop units, commonly referred to as RTUs, are packaged air conditioning systems installed on the roofs of commercial buildings, such as shops and small businesses. These units are designed to provide air conditioning to specific areas within a building. RTUs are favored for their simplicity, compactness, and self-contained nature, making them an efficient choice for distributing conditioned air through a building’s ductwork.
RTUs share similarities with air handling units (AHUs), but there are notable differences. While AHUs are often part of larger systems connected to central plants like chillers and boilers, RTUs are standalone units that house all necessary components. Additionally, RTUs are specifically designed to withstand outdoor elements, as they are always installed on rooftops.
There are several types of RTUs, each catering to different needs. Let’s explore four common variations:
These units exclusively use 100% fresh air, with no recirculation. An external exhaust fan typically removes the return air to maintain balanced air pressure within the building.
Some RTUs are designed to recirculate internal air, which can be energy-efficient, especially during colder months. These units feature return air dampers that work in conjunction with intake air dampers to adjust the mix of fresh and return air.
These units allow for some or all of the air to be expelled to the atmosphere, depending on the temperature of the outside and return air. This feature helps optimize energy usage by adjusting the air mix.
Increasingly popular for their energy efficiency, these units incorporate a heat wheel. The heat wheel is a rotating heat exchanger that transfers waste heat from the return air to the incoming fresh air, enhancing energy conservation without mixing the two air streams.
RTUs consist of several critical components that ensure their effective operation:
Rooftop units are integral to modern HVAC systems, providing efficient air conditioning solutions for commercial spaces. By understanding their types and components, you can appreciate their role in maintaining comfortable indoor environments. For further learning, consider exploring online resources like Danfoss Learning, which offers a wealth of information on engineering topics, including RTUs.
Thank you for engaging with this educational article. We hope it has enriched your knowledge of rooftop units and their significance in HVAC systems.
Engage with an online simulation tool that allows you to explore the inner workings of a rooftop unit. Adjust different parameters such as airflow, temperature, and damper positions to see how they affect the system’s performance. This hands-on activity will deepen your understanding of RTU operations and their impact on energy efficiency.
Analyze a real-world case study of a commercial building that implemented RTUs. Examine the decision-making process, the types of RTUs chosen, and the outcomes achieved. Discuss in groups how the RTUs improved the building’s HVAC efficiency and what lessons can be applied to future projects.
Participate in a workshop where you will identify and label the key components of a rooftop unit. Use physical models or detailed diagrams to locate parts such as the housing, air hood, dampers, filters, coils, and fans. This activity will reinforce your knowledge of each component’s function and importance.
Engage in a debate on the energy efficiency of different types of RTUs. Prepare arguments for and against the use of fresh air only units, recirculating units, return air damper units, and heat wheel units. This exercise will enhance your critical thinking and understanding of the trade-offs involved in RTU selection.
Organize a field trip to a commercial building with rooftop units installed. Observe the RTUs in action and speak with facility managers about their experiences with these systems. This real-world exposure will provide practical insights into the installation, maintenance, and performance of RTUs.
Sure! Here’s a sanitized version of the YouTube transcript:
—
Hello everyone, Paul here from TheEngineeringMindset.com. In this video, we will be discussing rooftop units. We’ll cover what an RTU is, where they are used, how they work, the different types, and the components inside, such as heat exchangers, filters, fans, ductwork, grilles, and air hoods.
If you enjoy the information on this channel, I hope you do, you can continue your education by visiting Danfoss Learning, who have kindly sponsored this video. Danfoss aims to encourage people worldwide to learn as much as possible about engineering. They have created a free online learning platform filled with courses on various engineering topics, including additional lessons about rooftop units. To get started, click the link in the video description below, create your free Danfoss Learning profile, and choose your first class.
Now, let’s dive into rooftop units. As the name suggests, rooftop units, or RTUs for short, are located on the roofs of shops and small commercial buildings to provide air conditioning to specific areas. These are packaged air conditioning units, popular for being simple, compact, and self-contained. Their purpose is to distribute conditioned air within defined areas of a building. Rooftop units are connected to ductwork, which provides a defined route for the conditioned air to travel.
In our last video, we discussed air handling units (AHUs). If you haven’t watched that yet, I encourage you to do so; links are in the video description. You’ll notice that rooftop units are quite similar to AHUs. The main difference is that RTUs are usually more compact and always installed on the roof, requiring them to be more robust and weatherproof to withstand elements like sun, rain, snow, and wind. While AHUs are often connected to central plants like chillers and boilers, RTUs are self-contained with everything they need in one unit.
There are many types of rooftop units, and we’ll look at four typical versions, starting with the most basic. The first unit is fresh air only, meaning there’s no recirculation of air. It takes 100% fresh air and conditions it. The return air is usually removed by an external exhaust fan to balance the air pressure within the building.
First, we have the housing, which protects all the mechanical and electrical equipment inside the unit from the elements. There are access panels for engineers to perform maintenance. At one end, there is typically an air hood that draws in outside ambient air. The hood is designed to prevent water, snow, and debris from entering the unit, and there is usually a mesh across the inlet to prevent wildlife and objects from causing blockages.
Next, we might find dampers. Not every unit has these, but newer models typically do. These are sheets of metal that rotate together to open fully and allow air to enter or close to seal the unit. Some dampers can vary their open position, especially if recirculation is used.
After the dampers, we have filters that slide out from the service door. Their purpose is to clean the air by capturing dirt and dust from the incoming fresh air. Without filters, dust would accumulate on the fan, heat exchangers, and ductwork, reducing the machine’s effectiveness and efficiency.
Following the filters, we find coils used to cool or heat the air by adding or removing thermal energy. Depending on the location and ambient conditions, some units will be cooling only, heating only, or both. If cooling only, there is typically a single coil connected to a refrigeration unit. If heating only, it may be connected to a heat pump, gas burner, or electrical heating element. Units that provide both heating and cooling may have two heat exchangers or a single coil connected to a heat pump.
Most units use a refrigeration system for cooling. The compressor, condenser, fan, and controls are usually located at the rear or side of the unit to reject heat and keep it away from the intake and conditioned air.
After the coils, we find the fan, usually a belt-driven centrifugal type or an energy-efficient EC type fan. The fan pulls air in from outside, through the dampers, filters, coils, and pushes it through the ductwork to distribute it around the building.
Some units may recirculate internal air for a return ductwork system, saving energy, especially in winter. This design includes a return air damper that works in sync with the intake air damper to change the mixture of fresh and return air.
Another common version includes a return air damper, where some or all of the air can be rejected to the atmosphere. The temperature of the outside air and return air will dictate how much air is rejected and how much is mixed and recirculated.
The final version we’ll look at has a heat wheel built into the unit, which is becoming more popular due to the need for energy efficiency. This unit pulls air in through the hood, controlled by the damper, and passes it through a filter before reaching the heat wheel. The heat wheel is a rotating heat exchanger that transfers waste heat from the return air to the incoming fresh air without mixing the two streams.
After the heat wheel, the air flows through another filter, and then the fan distributes it through the building via ductwork. The return air is pulled back into the RTU for the return ductwork, where it can either recirculate or pass through a filter and heat wheel to recapture waste heat.
Before we wrap up, I want to remind you to sign up for your free Danfoss Learning profile for access to over 1,500 e-lessons, including several about rooftop units.
Now, for the engineers quiz answers: I asked what the term package air conditioning unit means. The answer is that package air conditioners contain all the main components within one casing, including fans, filters, cooling and heating coils, compressors, and controls. The entire system is prefabricated into one package for quick installation.
Thank you for watching! I hope you found this helpful. If so, please like, subscribe, and share, and leave your questions in the comments below. You can also follow us on social media and visit TheEngineeringMindset.com. Thanks again for watching!
—
This version maintains the essential information while removing any informal language and ensuring clarity.
Rooftop – A flat or sloped surface at the top of a building, often used to install equipment such as HVAC systems in engineering applications. – The engineers decided to place the new solar panels on the rooftop to maximize energy efficiency.
Units – Standardized quantities used to measure and express physical properties in engineering and physics. – The laboratory experiment required all measurements to be recorded in SI units for consistency.
HVAC – An acronym for Heating, Ventilation, and Air Conditioning, referring to the systems used to regulate indoor environmental comfort. – The new building design incorporates an advanced HVAC system to improve air quality and energy efficiency.
Air – The invisible gaseous substance surrounding the earth, a mixture mainly of oxygen and nitrogen, crucial in various engineering applications. – The air pressure in the pneumatic system must be carefully monitored to ensure optimal performance.
Energy – The capacity to do work, which can exist in various forms such as kinetic, potential, thermal, electrical, chemical, and nuclear. – Engineers are constantly seeking new ways to harness renewable energy sources to reduce environmental impact.
Efficiency – The ratio of useful output to total input in any system, often used to measure the performance of machines and processes. – Improving the efficiency of the engine was a key focus in the redesign of the vehicle.
Components – Individual parts or elements that make up a larger system or machine in engineering. – The failure of one of the critical components led to the shutdown of the entire assembly line.
Circulation – The movement and distribution of fluids or gases within a system, essential for maintaining balance and function. – Proper circulation of coolant is vital to prevent overheating in the reactor core.
Temperature – A measure of the thermal energy within a system, indicating how hot or cold the system is. – The temperature sensors are calibrated to ensure accurate readings in the chemical processing plant.
Mechanical – Relating to machines or the principles of mechanics, often involving the design, construction, and use of machinery. – The mechanical properties of the new alloy were tested to determine its suitability for aerospace applications.
Cookie | Duration | Description |
---|---|---|
cookielawinfo-checkbox-analytics | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Analytics". |
cookielawinfo-checkbox-functional | 11 months | The cookie is set by GDPR cookie consent to record the user consent for the cookies in the category "Functional". |
cookielawinfo-checkbox-necessary | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookies is used to store the user consent for the cookies in the category "Necessary". |
cookielawinfo-checkbox-others | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Other. |
cookielawinfo-checkbox-performance | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Performance". |
viewed_cookie_policy | 11 months | The cookie is set by the GDPR Cookie Consent plugin and is used to store whether or not user has consented to the use of cookies. It does not store any personal data. |