In the world of building services engineering, it’s common to encounter duplicate equipment like pumps, fans, and compressors. This article delves into the reasons behind this redundancy, how these systems operate, and the mechanisms that control them. Sponsored by Telecontrols, a leader in automation since 1963, this discussion highlights the importance of load monitors in optimizing pump systems.
In commercial buildings, high-rise residential areas, industrial plants, and utility infrastructures, having duplicate mechanical equipment is crucial for ensuring reliability. The primary reason for this redundancy is to maintain operations if one unit fails. For instance, in a water supply system, two pumps are connected to the same pipe, but only one, known as the duty pump, operates at a time. The other, the standby pump, is ready to take over if needed. This setup is not limited to pumps; it applies to fans, chillers, and other critical equipment.
When the duty pump fails, the standby pump must seamlessly take over. This transition is managed by an alternating relay. Alternating relays are crucial for load matching as well. For example, in an office building, two sets of chillers might be used to provide cooling. During peak summer, both sets operate, but in winter, only one may be necessary. The standby set can support the duty set if it struggles to meet the demand.
Pumps that fill storage tanks are typically controlled by float switches. When the water level drops, the float switch triggers a relay to start the pump. Once the water level is adequate, the relay stops the pump. If a pump fails, the system is down until repairs are made. To prevent this, a second pump can be installed, with both pumps controlled by an alternating relay. This setup ensures that if the duty pump fails, the relay switches to the standby pump. Alternating control also prevents issues like seized bearings or rusted parts by ensuring both pumps have nearly equal run hours.
Consider a simple schematic of an alternating relay circuit controlling two compressors. A pressure transducer connects to the relay, which feeds the compressors. When system pressure falls, the transducer closes, allowing electricity to flow to compressor 1. The relay remains inactive until pressure rises, at which point the transducer opens, cutting power to compressor 1. If pressure drops again, the relay switches power to compressor 2, ensuring equal run time for both compressors.
In some scenarios, both pumps, fans, or compressors need to operate simultaneously, especially during high demand. Lead and lag sensors are used in such cases. The lead sensor detects a pressure drop and activates the duty compressor. If pressure continues to fall, the lag sensor activates the standby compressor. This setup ensures efficient operation and balanced wear on the equipment.
Today’s alternating relays incorporate solid-state electronics, offering additional features like maintenance overrides, time delays, and automatic fault changeover. These advancements enhance system reliability and efficiency, making them indispensable in modern building services engineering.
For more insights into electrical and controls engineering, explore additional resources and follow us on social media. Visit theengineeringmindset.com for further learning opportunities.
Engage with an online simulation tool that allows you to configure and test duplex relay systems. Experiment with different scenarios, such as pump failures or varying demand levels, to see how alternating relays manage transitions between duty and standby equipment. This hands-on activity will deepen your understanding of system redundancy and relay operations.
Analyze a case study of a commercial building or industrial plant that utilizes duplex relays. Identify the challenges faced and the solutions implemented. Discuss how redundancy and alternating relays contributed to system reliability and efficiency. Present your findings in a group discussion to enhance collaborative learning.
Create a schematic diagram of a relay control circuit for a hypothetical building system. Include components such as float switches, pressure transducers, and alternating relays. Explain your design choices and how they ensure continuous operation and balanced equipment usage. Share your design with peers for feedback and improvement suggestions.
Participate in a workshop that explores the latest advancements in relay technology, including solid-state electronics and smart features. Learn how these innovations improve system performance and reliability. Engage in hands-on activities to configure and test modern relay systems, gaining practical experience with cutting-edge technology.
Prepare a short presentation on the role of lead and lag sensors in building systems. Explain how these sensors work in conjunction with alternating relays to manage high demand scenarios. Teach your peers about the benefits of this setup, focusing on efficiency and equipment longevity. Use visual aids and real-world examples to enhance your presentation.
Sure! Here’s a sanitized version of the provided YouTube transcript:
—
[Applause][Music]
In this video, we will explore why we often find duplicates of equipment like pumps, fans, and compressors in building services engineering. We’ll discuss how these systems operate, why only one unit works at a time, and what controls them. This video is sponsored by Telecontrols, a leading manufacturer in the automation industry since 1963. Their load monitors provide peace of mind for heavy-duty monitoring and optimization of pump systems. You can learn more about their products by checking the link in the video description.
In commercial buildings, high-rise residential areas, industrial plants, and utilities infrastructure, it’s common to find duplicate mechanical equipment. The primary reason for this is redundancy; if one unit fails, the other can take over. For example, a pump set supplies water to a storage tank, which then distributes water to each floor. To ensure a constant water supply, two pumps are connected to the same pipe, but only one operates at a time. The operating pump is referred to as the duty pump, while the inactive one is the standby pump. Depending on the criticality of the pumping system, there may be multiple standby pumps for added safety. This concept also applies to fans, chillers, and other equipment.
If the duty pump fails, the standby pump must take over. This is managed using an alternating relay, which we will discuss later. Another reason for having duplicate equipment is load matching. For instance, an office building may have two sets of chillers to provide cooling. During peak summer, both chillers and pumps operate, but in winter, only one set may be needed. The standby set can provide support if the duty set cannot handle the load alone. Additionally, running pumps and fans simultaneously can save energy, but we won’t cover that in this video.
The pump that fills the storage tank is controlled by a float switch. When the water level drops too low, the float switch activates a relay to start the pump. When the water level is sufficient, the relay cuts power to the pump. If the pump fails, the system will be out of service until repairs are made. To address this, we can install a second pump and control both with an alternating relay. When the duty pump fails, the relay switches to the standby pump. However, if the standby pump hasn’t operated in a while, it may not start due to seized bearings or rusted parts. To prevent this, we can alternate the control of the pumps, ensuring they have nearly equal run hours and wear.
Here’s a simple schematic of an alternating relay circuit controlling two compressors. The pressure transducer connects to the relay, which feeds the compressors. As pressure in the system falls, the transducer closes, allowing electricity to flow to compressor 1. The alternating relay remains inactive. When the pressure increases to a satisfactory level, the transducer opens, cutting power to compressor 1. If pressure drops again, the relay diverts power to compressor 2, ensuring equal run time for both compressors.
Now, let’s look at a simplified alternating relay circuit with three solenoids and ten switches controlling two fans. The main switch turns the entire circuit on and off. When the main switch is closed, current flows through the switches, energizing solenoid 1, which activates the fans. When the main switch opens, the current stops, de-energizing the solenoids and turning off the fans. This process can be simplified using an alternating relay.
Sometimes, both pumps, fans, or compressors need to run simultaneously, especially when demand is high. In such cases, we can use lead and lag sensors. The lead sensor detects a drop in pressure and activates the duty compressor. If pressure continues to drop, the lag sensor activates the standby compressor.
This simplified example illustrates how the system works. Modern alternating relays use solid-state electronics and offer additional functions such as maintenance override, time delays, and automatic fault changeover.
That’s it for this video! You can continue learning about electrical and controls engineering by clicking on one of the videos on screen now. Don’t forget to follow us on social media and visit theengineeringmindset.com for more resources.
—
Feel free to let me know if you need any further modifications!
Redundancy – The inclusion of extra components or systems that are not strictly necessary to functioning, intended to increase reliability in case of failure of other components. – In aerospace engineering, redundancy is crucial to ensure that critical systems continue to operate even if one component fails.
Pumps – Devices used to move fluids or gases by mechanical action, typically converting electrical energy into hydraulic energy. – The engineers designed a series of pumps to efficiently circulate coolant throughout the power plant.
Relays – Electrically operated switches used to control a circuit by a low-power signal, or where several circuits must be controlled by one signal. – In the control system, relays were used to manage the switching of high-voltage circuits safely.
Sensors – Devices that detect and respond to input from the physical environment, such as temperature, pressure, or motion. – The automated system relies on sensors to monitor and adjust the environmental conditions within the laboratory.
Compressors – Machines that increase the pressure of a gas by reducing its volume, commonly used in refrigeration and air conditioning systems. – The HVAC system’s efficiency was improved by upgrading to more advanced compressors.
Engineering – The application of scientific and mathematical principles to design and build structures, machines, and systems. – Engineering students must understand the principles of thermodynamics to design efficient engines.
Systems – Complex networks of components that work together to perform a specific function or set of functions. – The integration of renewable energy sources into existing power systems is a major focus of modern engineering.
Operation – The functioning or performance of a machine, process, or system. – The operation of the new manufacturing line was optimized to reduce waste and increase productivity.
Control – The regulation or manipulation of variables within a system to achieve desired outcomes. – Advanced control algorithms were implemented to maintain the stability of the robotic arm during precision tasks.
Efficiency – The ratio of useful output to total input, often used as a measure of how well a system performs. – Improving the thermal efficiency of the engine resulted in significant fuel savings.
Cookie | Duration | Description |
---|---|---|
cookielawinfo-checkbox-analytics | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Analytics". |
cookielawinfo-checkbox-functional | 11 months | The cookie is set by GDPR cookie consent to record the user consent for the cookies in the category "Functional". |
cookielawinfo-checkbox-necessary | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookies is used to store the user consent for the cookies in the category "Necessary". |
cookielawinfo-checkbox-others | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Other. |
cookielawinfo-checkbox-performance | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Performance". |
viewed_cookie_policy | 11 months | The cookie is set by the GDPR Cookie Consent plugin and is used to store whether or not user has consented to the use of cookies. It does not store any personal data. |